Answer service override: For installations that use answering services provided by the phone company. Two
separate calls must be made to the system for the panel to answer. On the first call, let
the phone ring twice and hang up. Call a second time, and the panel will answer on
the first ring and respond with an access confirmation tone.
NOTE: For remote phone access to work correctly, the panel must be wired for full
phone line seizure using an RJ-31X connection.
After the system confirmation tone, enter a valid disarm code that is programmed for
remote phone access within 15 seconds. The system will respond with system status.
Remote phone access operates in the same manner as local phone access, however, all
arming state changes are echoed over the inside house speakers. During remote phone
access, local phone access is unavailable and all local phones will receive a system
beep every second signifying remote phone access is active.
NOTE: Some electronic phone systems use the * and # keys for additional functions. It
may be required that the * and # are pressed twice for the system to generate the * or #
tone.
System Access Codes
PC Access Code: Code required for programming the panel via computer software.
Program Access Code: Code required to place the system into program mode.
Local Phone Access Code: Code required to access the system from a local phone.
Secured Access Code: Code required for a central station to access the panel during two-way callback if the
secured callback option is selected.
System Times
Entry delay 1 and 2: The system provides two different entry delay times for exterior and interior delay zone
types. Each of these times is programmable from 1 to 255 seconds. Not to exceed 45
seconds in a UL installation.
Exit delay: An exit delay time may be programmed for 1 to 255 seconds. Not to exceed 60
seconds in a UL installation.
Alarm cut off and reset: The system provides for an automatic reset (cut off high volume tones and system reset)
in the range of 1 to 255 minutes. This time will also control the Any Activation control
channel. Not to be less than 4 minutes in a UL installation.
Duration between fire, For zone trouble, transmitter tamper, or a fire zone alert condition, a supervisory beep
tamper, trouble chirps: will be sounded at intervals determined by this time. For all activations except the fire
chirp, the tone can be silenced by checking status. Valid times are from 1 to 255
seconds. If a value of 000 is programmed, this feature is disabled. This feature must be
enabled in a UL installation.
Duration for recognition For systems with a back up battery, the system can determine when AC power is lost.
of AC power loss: This location determines the time period in minutes before the system will recognize
the power loss and speak "POWER OFF." If the communicator is programmed, it will
send a report to the central station. Valid AC power loss recognition times are from 1 to
255 minutes. This feature must be enabled in a UL installation.