TS16 - Only use between 32 - 127 degrees F
Temperatures from a TS16 can be used as a zone input. The system will prompt:
2 digit input number: The system supports up to 16 separate TS16s. Enter the TS16 address to be used. Legal
values are 1 - 16. Use the locations below to program the TS16. A temperature at or
above the High point is an open. A temperature at or below the Low temperature is an
open. The hysteresis setting determines how far the temperature must rise (above Low
setting) or fall (below High setting) for the zone to restore. TS16 inputs are not evaluated
for UL installation.
Options - Enter Total Location Value
Enable TS16
.......................................................................................................................
001
Speak all temperature transmissions
..................................................................................
002
Speak when time is requested
...........................................................................................
004
Open zone at High Temperature setting
............................................................................
016
Open zone at Low Temperature setting
.............................................................................
032
Hysteresis 2 degrees
..........................................................................................................
064
Hysteresis 4 degrees
..........................................................................................................
128
Default (TS16 disabled)
.....................................................................................................
000
Note: If a Low setpoint and High setpoint are being used then: Low + hysterics must be less then High - hysterics.
Hysterics settings of 2 and 4 can be added (192) for a hysterics of 6 degrees. If values 64 and 128 are not
used, the hysteresis is 1 degree.
Alarm Point Transmitters - Supervised
7 digit serial number: Enter the serial number listed on the bar code label. Only enter the seven numbers. The
leading letter on the label is not used.
Accept serial number: If the serial number is correct, press F2. Otherwise, press monitor and enter the correct
value.
The following is only prompted on multiloop transmitters:
1 digit input number: Use the transmitter loop locations to determine the input.
Loop 1
(Shock Input)
Loop 1
Loop 2
5816 (MN) 5817
Loop 3Loop 2Loop 1
5819
Loop 3
Loop 2