86
Lutron® integration protocol
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) / Get (?) Zone Level 1 Level = 0 or 100.00
1
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising Lowering 4 None
Report Travel Time Remaining
5
17 Travel time in seconds: 0 – 255
Motor Jog Raise
6
18 None
Motor Jog Lower
6
19 None
Motor 4-Stage Jog Raise
6
20 None
Motor 4-Stage Jog Lower
6
21 None
NOTES
1. Setting the level to 0% will cause the output to travel in the Closed direction; setting the level to 100% will cause the
output to travel in the Open direction; setting any level from 1 – 99% will be ignored by the output. Querying its level will
report 0 or 100%, based on the last direction it moved.
2. Fade is not available for Shades because they move at a constant rate. The parameter must be entered, but is ignored.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter-second. For example, if a delay time is specified
as 1.45 seconds, a value of 1.25 seconds will be used.
4. The delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is 0.25
seconds; the maximum delay time is 4 hours.
5. If the travel time of a motor is greater than 255 seconds, the unit will report 255 until the travel time drops below that
value.
6. Not supported in QS Standalone.
OUTPUT Command Format
Energi Savr NodeTM QS
for Motor Module (International) (continued)
OUTPUT Commands
Operation
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Command
Integration ID (example)
#OUTPUT, 3, Action Number, Parameters