Installation
7
NXB-CCG NetLinx® Clear Connect™ Gateway
Ethernet Pin Numbering
The numbering for pins in the Ethernet port is as follows:
Returning an NXB-CCG to Factory Default Settings
1.
Press and hold the Reset button (FIG. 1) on the device for 20 seconds.
2. The Power/Status LED will start flashing slowly for approximately10 seconds, after which it will start
rapidly flashing for approximately 20 seconds and then remain on.
3. The device has been returned to its factory default settings.
FIG. 5 Ethernet Pin Numbering
Ethernet Pin Numbering
Ethernet: Pin #:
T+Ve 1
T-Ve 2
R+Ve 3
R-Ve 6
Returning an NXB-CCG to factory default settings will erase all programming from it
and all system devices and will require all Clear Connect devices to be
reprogrammed into the system
Returning the NXB-CCG to its factory default settings does not do the same for any
connected Lutron Clear Connect devices. They may have to be returned to factory
defaults separately before being reattached to the NXB-CCG’s network.