Przeglądanie stron 37
NXC-VAI4 Analog Voltage Control Card
30
NetLinx Cardframe, Control Cards, and NetModules
NXC-VAI4 Output Level Assignments
NXC-VAI4 Channel Assignments (Cont.)
Channel State Function
17
ON While channel 17 is ON, the voltage on Output 4 is set to 0%
OFF Sets Output 4 voltage to 50%.
18
ON While channel 18 is ON, the voltage on Output 1 is set to 75%
OFF Sets Output 1 voltage to 50%.
19
ON While channel 19 is ON, the voltage on Output 2 is set to 75%
OFF Sets Output 2 voltage to 50%.
20
ON While channel 20 is ON, the voltage on Output 3 is set to 75%
OFF Sets Output 3 voltage to 50%.
21
ON While channel 21 is ON, the voltage on Output 4 is set to 75%
OFF Sets Output 4 voltage to 50%.
22
ON While channel 22 is ON, the voltage on Output 1 is set to 25%
OFF Sets Output 1 voltage to 50%.
23
ON While channel 23 is ON, the voltage on Output 2 is set to 25%
OFF Sets Output 2 voltage to 50%.
24
ON While channel 24 is ON, the voltage on Output 3 is set to 25%
OFF Sets Output 3 voltage to 50%.
25
ON While channel 25 is ON, the voltage on Output 4 is set to 25%
OFF Sets Output 4 voltage to 50%.
NXC-VAI4 Output Level Assignments
Level Description
1
8 bit field; sets voltage on Output 1 to the value commanded.
The range is 0-255.
Conflicts with channels 1, 5, 10, 14, 18, 22.
2
8 bit field; sets voltage on Output 2 to the value commanded.
The range is 0-255.
Conflicts with channels 2, 6, 11, 15, 19, 23.
3
8 bit field; sets voltage on Output 3 to the value commanded.
The range is 0-255.
Conflicts with channels 3, 7, 12, 16, 20, 24.
4
8 bit field; sets voltage on Output 4 to the value commanded.
The range is 0-255.
Conflicts with channels 4, 8, 13, 17, 21, 25.
5
8/16 bit field; commands that Output 1 be set to "CURRENT OUTPUT 1 SPEED" of the appropriate
polarity until the voltage read at Input 1 is within "INPUT 1 MAXIMUM DEVIATION" of this value.
Conflicts with channels 1, 5, 10, 14, 18, 22.
6
8/16 bit field; commands that Output 2 be set to "CURRENT OUTPUT 2 SPEED" of the appropriate
polarity until the voltage read at Input 2 is within "INPUT 2 MAXIMUM DEVIATION" of this value.
Conflicts with channels 2, 6, 11, 15, 19, 23.
7
8/16 bit field, commands that Output 3 be set to "CURRENT OUTPUT 3 SPEED" of the appropriate
polarity until the voltage read at Input 3 is within "INPUT 3 MAXIMUM DEVIATION" of this value.
Conflicts with channels 3, 7, 12, 16, 20, 24.
8
8/16 bit field, commands that Output 4 be set to "CURRENT OUTPUT 4 SPEED" of the appropriate
polarity until the voltage read at Input 4 is within "INPUT 4 MAXIMUM DEVIATION" of this value.
Conflicts with channels 4, 8, 13, 17, 21, 25.